Product Center


平度Recessed horizontal fan coil unit

Water system air conditioning terminal heat exchange and air supply products, suspended and concealed inside the ceiling; For standard operating parameters, cooling: 7℃ chilled water; heating: 60℃ low-temperature hot water; Does not include return air box and temperature control switch. Condensate drainage must be considered for summer cooling.

Category:

平度Fan coil unit

Phone: 024-89722880

Product Description

Model Name
FP-WA Recessed Horizontal Fan Coil Unit

Main Use
Water system air conditioning terminal heat exchange and air supply.

Place of Use
Recessed installation in the ceiling.

Product Introduction
Water system air conditioning terminal heat exchange and air supply product, recessed installation inside the ceiling;
These are standard operating parameters: Cooling: 7℃ cold water; Heating: 60℃ low-temperature hot water;
Does not include return air box and temperature control switch. Condensation drainage should be considered for summer cooling.

Main Parameters

Model Length*Width*Height mm Heating Capacity kW Cooling Capacity kW Inlet/Outlet Pipe Diameter Input Power W (220V) Air Volume m³ 3/h
FP-34WA 710*477*230 3.39 1.98 DN20 37 340
FP-51WA 810*477*230 4.5 2.8 DN20 52 510
FP-68WA 950*477*230 6.35 3.87 DN20 62 680
FP-85WA 1050*477*230 7.45 4.58 DN20 76 850
FP-102WA 1150*477*230 9.22 5.42 DN20 96 1020
FP-136WA 1350*477*230 12.4 7.38 DN20 134 1360
FP-170WA 1650*477*230 16.3 9.08 DN20 152 1700
FP-204WA 1850*477*230 19.5 11.1 DN20 189 2040
FP-238WA 1950*477*230 20.2 12.9 DN20 228 2380

Remarks:
1. Cooling capacity operating parameters: Inlet air dry-bulb temperature 27℃, wet-bulb temperature 19.5℃, inlet water temperature 7℃, water temperature difference 5℃.
2. Heating capacity operating parameters: Inlet air dry-bulb temperature 21℃, inlet water temperature 60℃, hot water flow rate same as cooling operating conditions.
3. Input power operating parameters: Operating pressure 12pa.

Precautions
It is recommended to increase the selection, and winter antifreeze protection should be done.

 

 