Fresh Air Series Steam Heater
Keywords:
Category:
- Description
-
Model Name
NF-GS(Q)ZBXF Fresh Air Heating Type
Main Use
Product for sidewall installation and horizontal air supply.
Place of Use
Factories, warehouses, garages, and farms.
Product Introduction
◎ Fresh air heating equipment using steam below 0.4MPa or hot water above 70℃;
◎ Heats fresh air, preventing indoor temperature drop due to fresh air replenishment, suitable for places requiring large amounts of ventilation;
◎ Uses a carbon steel pipe wound aluminum finned heat exchanger, with thick pipe walls, good low-temperature antifreeze performance;
◎ The machine connects to the wall fresh air inlet, the air duct is equipped with an electric insulated air valve, and it works with the fan;
◎ An insect screen, rain cover, and filter screen need to be installed on the outside of the wall, and a custom control box is required;
◎ If the water temperature or outdoor temperature is low, a pipe electric heater needs to be installed at the front to preheat the fresh air;
◎ Available in high-temperature hot water and steam types. If the water temperature is low, an auxiliary electric heater needs to be added for preheating.
◎ High-temperature hot water type
Water pipes can enter and exit from the same side or both sides, bottom inlet and top return, threaded connection, flange optional.
◎ Steam type
Water pipes can be installed vertically or horizontally, top inlet and bottom outlet, with flange, drain valve required for return water;
It is recommended to use pressure below 0.2MPa to reduce the impact of high temperature on the motor from the heat exchanger;
Use above 0.2MPa pressure requires a solenoid valve, the valve must be closed when the fan stops;
If no solenoid valve is installed, local high temperature around the heat exchanger may trigger motor thermal protection or damage.
Main Parameters
High-temperature hot water typeModel Length * Width * Height mm Motor Power W(380V) Air Volume m³ 3/h Inlet and Outlet Pipe Diameter Inlet/Outlet Water 70/60℃ Inlet/Outlet Water 80/65℃ Inlet/Outlet Water 90/70℃ Heating Capacity kW Heating Capacity kW Heating Capacity kW NF-GS25ZBXF 600*650*715 190 2500 DN32 21 26 32 NF-GS37ZBXF 730*650*800 250 3700 DN40 31 39 47 NF-GS60ZBXF 900*700*985 550 6000 DN50 50 63 77 NF-GS80ZBXF 1000*700*1120 850 8000 DN50 67 84 102
Steam typeModel Length * Width * Height mm Motor Power W(380V) Air Volume m³ 3/h Inlet and Outlet Pipe Diameter Steam Pressure 0.1MPa Steam Pressure 0.2MPa Steam Pressure 0.3MPa Heating Capacity kW Heating Capacity kW Heating Capacity kW NF-Q25ZBXF 600*650*715 190 2500 DN25 28 37 42 NF-Q37ZBXF 730*650*800 250 3700 DN32 41 54 62 NF-Q60ZBXF 900*700*985 550 6000 DN32 67 88 101 NF-Q80ZBXF 1000*700*1120 850 8000 DN40 88 117 134
Notes
Customizable according to construction drawings or bidding parameters.
Related products
Product inquiry
SHENYANG ACT TECHNOLOGY CO.,LTD.
Tel:+86-13804980877
Email:act88272927@163.com
Address: Qianyaobao Village, Qingshui Street, Shenbei New District, Shenyang City
Technology Department:+86-24-31329998
Purchasing Department:+86-24-31329977
WeChat